Skip to content

Professional Online UPS 220V / 230V / 240V 1000VA

OL1000HV

Double-conversion online UPS rated 1000 VA for 220/230/240 V mains, with output power factor 1 and voltage regulation under 1%. Programmable outlets control load segments independently during power failure.

Features

  • True double-conversion – output power factor is 1 (maxium), which means all of the power supplied is being used for productive work and makes work the most efficient
  • Output voltage regulation < 1% – provides higher performance and efficiency for critical applications
  • Programmable power management outlets – users can easily and independently control load segments. During power failure, this feature enables users to extend battery time to mission-critical devices by shutting down noncritical devices
  • Emergency Power Off function (EPO) – EPO connector at rear panel allows emergency UPS Power Off from a remote location
  • SNMP + USB + RS-232 multiple communications – allows either USB or RS-232 communication ports to work with SNMP interface simultaneously
  • Hot swappable battery design – all potential UPS maintenance, including complete power module exchange, can be performed without powering down connected equipment As long as utility power is on, users can leave the UPS and connected equipment on while replacing the battery
  • ECO mode for energy saving – offers up to 97% effi ciency to cut energy usage and cost. UPS power application via static bypass timely returns to online double conversion when the need arises
  • Provides over-voltage cut-off protection and surge immunity by MOV for full-time equipment protection
  • High power factor charger up to 1000W capacity with very low ripple current when charging battery
  • Multi-functional LCD interface – displays immediate, detailed information on input voltage, battery capacity, power status, battery status, operating status, and assessed backup runtime, etc
  • Smart battery charger design to optimize battery performance – adjusts charging voltage according to outside temperatures and extends the useful service life of batteries

General

UPS Topology
Double-Conversion
Energy Saving(max)
>96%(ECO) >89%(AC) >88%(Batt)
HID Compliant USB Port
Yes
Serial Port
Yes
SNMP / HTTP Remote Monitoring
Yes - Optional SNMP CARD

Input

Voltage
220/230/240 VAC
Input Voltage Range
160-300 VAC ± 5% @ 100% load 110-300 VAC ± 5% @ 50% load Derate capacity to 80% when the output voltage is adjusted to 200VAC/208VAC.
Input Frequency Range
40 Hz ~ 70 Hz
Rated Input current
4.8A
Input Power Factor
≧ 0.99 @ nominal voltage (100% load)
Cold Start
Yes
Plug Type
IEC 320 C14
Power cord
6ft (Schuko Plug/UK Plug/AU Plug/IEC Plug)

Output

VA
1000
Watts
1000
On Battery Waveform
Sine Wave
On Battery Frequency
50/60Hz +/- 0.1 Hz
Outlets - Total
8
Outlet Type
(8) IEC 320 C13
Outlets - Battery & Surge Protected
8
Rated Power Factor
1
Crest Factor
3:1
Harmonic Distortion
≦2 % THDi (Linear Load) ≦ 4 % THDi (Non-linear Load)
Voltage Regulation
± 1%(Batt)
Transfer Time(AC to Batt.)
0ms
Transfer Time(Inverter to Bypass)
4ms(ECO)

Battery

Runtime at Half Load (min)
9.44
Runtime at Full Load (min)
3.10
Battery Type
Sealed Lead-Acid
Battery Pack Voltage
24V
Battery Size
12V/9AH
Battery Quantity
2
Hot-Swappable
Yes
Typical Recharge Time
3 hours recover to 95% capacity@2A charging current. Max charger current 12A
Extended Battery Module
BP24V18AH
Replacement Battery Pack
BC24V9AH
Replacement Battery Pack Quantity
1

Physical Properties

Rack Unit
2U
Type
Rack/Tower
Dimensions (L x W x H)
8.80 x 43.80 x 41.00 cm (3.46 x 17.24 x 16.14 in.)
Weight
12.70 kg ( 27.97 lb )

Environmental

Temperature (Operating / Storage)
0–40°C (non-condensing) / -20 – 50°C
Humidity (Operating & Storage)
20–90 % RH / 10% – 95%(No condensing)
Audible noise at 1M from surface of unit
Less than 50dB

Certifications

Certifications
CE
Approvals
RoHS
Package Contents
1x Rack Mounting Kit 1x Rail Slide Kit 1x RS-232 Cable 1x USB Type A to B Cable 4x Power Cable (1xIEC C13/C14+ 1xIEC C13/Schuko+1xIEC C13/UK +1xIEC C13/AU(10A)) 1x Tower Stand Set
Note
For some of rack mount products, please note that the standard physical dimensions of WxDxH are expressed using a LxWxH format.