Skip to content

As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (eco PDUs) to effectively increase the efficiency of data center power usage.

Features

  • Connections
  • Supports 10/100Mbit Ethernet, Modem, RS-232, Daisy Chain interface
  • Supports TCP/IP, PPP, UDP, HTTP, HTTPS, SSL, STP, DCHP, ARP, NTP, DNS, Telnet, Auto Sense, Ping, SNMP V1,V2&V3, IPv6
  • Supports three-level account/password security, IP/MAC filter, 128 bit SSL, RADIUS, TACACS+, LDAP, LDAPS and Active Directory
  • Supports CC2000, eco Sensors, Java API, multiple Browsers (IE, Firefox, Chrome, Safari), OOBC/RS232
  • Metering
  • PDU and outlet level power metering and monitoring
  • Environment monitoring – supports external temperature/temperature & humidity sensors for rack temperature and humidity monitoring
  • Current, voltage, power, power dissipation, temperature, and humidity metering and threshold level setting
  • Outlet Switch Control
  • Remote power outlet control (On/Off, Power Cycle) by individual outlets and outlet groups
  • Outlet group support at the PDU and daisy chain level
  • Daisy chain with PON In – PON Out port
  • On/Off scheduling for individual outlets and outlet groups – power management tasks can be scheduled on a daily, weekly, monthly, or user-specified basis
  • Supports multiple power control methods – Wake on LAN, System After AC Back, Kill the Power
  • Power-On sequencing – users can set the power-on sequence and delay time for each outlet to allow equipment to be powered on in the correct order
  • Critical load outlet – keeps power always on for critical load devices
  • Proactive overload protection – automatically powers off the last outlet that caused the current overload

Electrical

Nominal Input Voltage
100 – 240 VAC
Nominal Input Voltage
100 – 240 VAC
Maximum Input Current
30A(Max); 24A(UL de-rated)
Maximum Input Current
32A(Max)
Input Frequency
50-60 Hz
Input Frequency
50-60 Hz
Input Connection
NEMA L6-30P
Input Connection
IEC 60309 32A
Input Power
6240 VA(Max); 4992 VA(UL de-rated)
Input Power
7360 VA(Max)
Outlet Type
Total: 21 x IEC320 C13 + 3 x IEC320 C19 Bank1-1: Outlet 1 – 8; 7 x C13 + 1 x C19 Bank1-2: Outlet 9 – 16; 7 x C13 + 1 x C19 Bank2: Outlet 17 – 24; 7 x C13 + 1 x C19
Outlet Type
Total: 21 x IEC320 C13 + 3 x IEC320 C19 Bank1-1: Outlet 1 – 8; 7 x C13 + 1 x C19 Bank1-2: Outlet 9 – 16; 7 x C13 + 1 x C19 Bank2: Outlet 17 – 24; 7 x C13 + 1 x C19
Nominal Output Voltage
100 – 240 VAC
Nominal Output Voltage
100 – 240 VAC
Maximum Output Current (Outlet)
C13: 15A(Max); 12A(UL de-rated) C19: 15A(Max); 12A(UL de-rated)
Maximum Output Current (Outlet)
C13: 10A(Max) C19: 16A(Max); TUV De-rated 15A(Max)
Maximum Output Current (Bank)
15A(Max); 12A(UL de-rated)
Maximum Output Current (Bank)
16A(Max); TUV De-rated 15A(Max)
Maximum Output Current (Total)
30A(Max); 24A(UL de-rated)
Maximum Output Current (Total)
32A(Max); TUV De-rated 30A(Max)
Breakers
2 x 16A UL489 Breaker
Breakers
2 x 16A UL489 Breaker
Metering
Outlet Level Current, Voltage, VA , PF and kWh Monitoring
Metering
Outlet Level Current, Voltage, VA , PF and kWh Monitoring
Outlet Switching
Bank1-1: None Bank1-2: Yes Bank2: Yes
Outlet Switching
Bank1-1: None Bank1-2: Yes Bank2: Yes
Environment Sensor Ports
4
Environment Sensor Ports
4
Metering Accuracy
Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Metering Accuracy
Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%

Physical Properties

Dimensions (L x W x H)
177.5 x 6.6 x 4.4 cm
Dimensions (L x W x H)
177.5 x 6.6 x 4.4 cm
Weight
6.4 kg
Weight
6.4 kg
Power Cord Length
1.6 m
Power Cord Length
1.6 m

Environmental

Temperature (Operating / Storage)
0–50°C / -20–60°C
Temperature (Operating / Storage)
0–40°C / -20–60°C
Humidity (Operating & Storage)
0–80% RH, Non-Condensing
Humidity (Operating & Storage)
0–80% RH, Non-Condensing

Compliance

EMC Verification
FCC, Others by Request
EMC Verification
CE, C-Tick, Others by Request
Safety Verification
PSE, Others by Request
Safety Verification
GOST, Others by Request
Note
For some of rack mount products, please note that the standard physical dimensions of WxDxH are expressed using a LxWxH format.

Firmware