As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (eco PDUs) to effectively increase the efficiency of data center power usage.
Features
- Connections
- Supports 10/100Mbit Ethernet, Modem, RS-232, Daisy Chain interface
- Supports TCP/IP, PPP, UDP, HTTP, HTTPS, SSL, STP, DCHP, ARP, NTP, DNS, Telnet, Auto Sense, Ping, SNMP V1,V2&V3, IPv6
- Supports three-level account/password security, IP/MAC filter, 128 bit SSL, RADIUS, TACACS+, LDAP, LDAPS and Active
- Directory
- Supports CC2000, eco Sensors, Java API, multiple Browsers (IE, Firefox, Chrome, Safari), OOBC/RS232
- Metering
- PDU and outlet level power metering and monitoring
- Environment monitoring – supports external temperature/temperature & humidity sensors for rack temperature and humidity monitoring
- Current, voltage, power, power dissipation, temperature, and humidity metering and threshold level setting
- Outlet Switch Control
- Remote power outlet control (On/Off, Power Cycle) by individual outlets and outlet groups
- Outlet group support at the PDU and daisy chain level
- Daisy chain with PON In – PON Out port
- On/Off scheduling for individual outlets and outlet groups – power management tasks can be scheduled on a daily, weekly, monthly, or user-speci¬ ed basis
- Supports multiple power control methods – Wake on LAN, System After AC Back, Kill the Power
- Power-On sequencing – users can set the power-on sequence and delay time for each outlet to allow equipment to be powered on in the correct order
Electrical
- Nominal Input Voltage
- 100 – 240 VAC
- Nominal Input Voltage
- 100 – 240 VAC
- Maximum Input Current
- 30A(Max); 24A(UL de-rated)
- Maximum Input Current
- 32A(Max)
- Input Frequency
- 50-60 Hz
- Input Frequency
- 50-60 Hz
- Input Connection
- NEMA L6-30P
- Input Connection
- IEC 60309 32A
- Input Power
- 6240 VA(Max); 4992 VA(UL de-rated)
- Input Power
- 7360 VA(Max)
- Outlet Type
- Total: 21 x IEC320 C13 + 3 x IEC320 C19 Bank1-1: Outlet 1 – 8; 7 x C13 + 1 x C19 Bank1-2: Outlet 9 – 16; 7 x C13 + 1 x C19 Bank2: Outlet 17 – 24; 7 x C13 + 1 x C19
- Outlet Type
- Total: 21 x IEC320 C13 + 3 x IEC320 C19 Bank1-1: Outlet 1 – 8; 7 x C13 + 1 x C19 Bank1-2: Outlet 9 – 16; 7 x C13 + 1 x C19 Bank2: Outlet 17 – 24; 7 x C13 + 1 x C19
- Nominal Output Voltage
- 100 – 240 VAC
- Nominal Output Voltage
- 100 – 240 VAC
- Maximum Output Current (Outlet)
- C13: 15A(Max); 12A(UL de-rated) C19: 15A(Max); 12A(UL de-rated)
- Maximum Output Current (Outlet)
- C13: 10A(Max) C19: 16A(Max); TUV De-rated 15A(Max)
- Maximum Output Current (Bank)
- 15A(Max); 12A(UL de-rated)
- Maximum Output Current (Bank)
- 16A(Max); TUV De-rated 15A(Max)
- Maximum Output Current (Total)
- 30A(Max); 24A(UL de-rated)
- Maximum Output Current (Total)
- 32A(Max); TUV De-rated 30A(Max)
- Breakers
- 2 x 16A UL489 Breaker
- Breakers
- 2 x 16A UL489 Breaker
- Metering
- Outlet Level Current, Voltage, VA , PF and kWh Monitoring
- Metering
- Outlet Level Current, Voltage, VA , PF and kWh Monitoring
- Outlet Switching
- Yes
- Outlet Switching
- Yes
- Environment Sensor Ports
- 4
- Environment Sensor Ports
- 4
- Metering Accuracy
- Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
- Metering Accuracy
- Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Physical Properties
- Dimensions (L x W x H)
- 177.5 x 6.6 x 4.4 cm
- Dimensions (L x W x H)
- 177.5 x 6.6 x 4.4 cm
- Weight
- 6.5 kg
- Weight
- 6.5 kg
- Power Cord Length
- 1.6 m
- Power Cord Length
- 1.6 m
Environmental
- Temperature (Operating / Storage)
- 0–50°C / -20–60°C
- Temperature (Operating / Storage)
- 0–40°C / -20–60°C
- Humidity (Operating & Storage)
- 0–80% RH, Non-Condensing
- Humidity (Operating & Storage)
- 0–80% RH, Non-Condensing
Compliance
- EMC Verification
- FCC, Others by Request
- EMC Verification
- CE, C-Tick, Others by Request
- Safety Verification
- PSE, Others by Request
- Safety Verification
- GOST, Others by Request
- Note
- For some of rack mount products, please note that the standard physical dimensions of WxDxH are expressed using a LxWxH format.
Firmware
Similar products

PE0316B
0U Basic PDU

PE0324B
0U Basic PDU

PE0116S
0U Basic PDU with Surge Protection

PE0216S
0U Basic PDU with Surge Protection

PE0224S
0U Basic PDU with Surge Protection

PE0316S
0U Basic PDU with Surge Protection

PE0324S
0U Basic PDU with Surge Protection

PE6108
15A/10A 8-Outlet 1U Metered & Switched eco PDU

PE5108
15A/10A 8-Outlet 1U Metered eco PDU

PE8108
15A/10A 8-Outlet 1U Outlet-Metered & Switched eco PDU

PE7108
15A/10A 8-Outlet 1U Outlet-Metered eco PDU

PE5221T