Skip to content

• 1U 8-Outlet eco PDU • Bank level meteringATEN has developed a new generation of green energy power distribution units (PDUs) to effectively increase the efficiency of data center power usage.

Features

  • Support 10/100Mbit Ethernet Interface
  • Support TCP/IP, UDP, HTTP, HTTPS, SSL, DHCP, SMTP, NTP, DNS, Auto Sense, Ping, Telnet, and SNMP V1,V2&V3
  • Support 2-level account/password security, IP/MAC filter, 128 bit SSL, RADIUS
  • Support : eco DC, Browser (IE, Firefox, Chrome, Safari)
  • Bank level power metering and monitoring
  • Environment Monitoring : support external temperature/temperature & humidity sensors for rack temperature and humidity monitoring
  • Current, voltage, power, power dissipation, temperature, and humidity metering and threshold level setting
  • Always On
  • Supports SMPTS, IPv6, Modbus (Over TCP/IP), Auto Ping, TLS1.2, SSH
  • Supports IEEE 802.1X
  • Authentication: LDAP, TACACS+
  • UI – heartbeat,schedule control, mail control, and setting rule

Electrical

Nominal Input Voltage
100 – 120 VAC
Nominal Input Voltage
100 – 240 VAC
Nominal Input Voltage
100 – 240 VAC
Maximum Input Current
20A Max; 16A(UL de-rated)
Maximum Input Current
20A Max; 16A(UL de-rated)
Maximum Input Current
16A Max
Input Frequency
50-60 Hz
Input Frequency
50-60 Hz
Input Frequency
50-60 Hz
Input Connection
NEMA L5-20P
Input Connection
PE5208B-ATA-J: NEMA L6-20P PE5208B-ATA-G: IEC 60320 C20
Input Connection
IEC 60320 C20
Input Power
2400 VA(Max); 1920 VA(UL de-rated)
Input Power
4160 VA(Max); 3328 VA(UL de-rated)
Input Power
3680 VA(Max)
Outlet Type
Total : 8 x NEMA 5-20R
Outlet Type
Total : 7 x IEC320 C13 + 1 x IEC320 C19
Outlet Type
Total : 7 x IEC320 C13 + 1 x IEC320 C19
Nominal Output Voltage
100 – 120 VAC
Nominal Output Voltage
100 – 240 VAC
Nominal Output Voltage
100 – 240 VAC
Maximum Output Current (Outlet)
NEMA 5-20R: 20A(Max); 16A(UL de-rated)
Maximum Output Current (Outlet)
C13: 15A(Max); 12A(UL de-rated) C19: 20A(Max); 16A(UL de-rated)
Maximum Output Current (Outlet)
C13: 10A(Max) C19: 16A(Max)
Maximum Output Current (Bank)
20A(Max); 16A(UL de-rated)
Maximum Output Current (Bank)
20A(Max); 16A(UL de-rated)
Maximum Output Current (Bank)
16A(Max)
Maximum Output Current (Total)
20A(Max); 16A(UL de-rated)
Maximum Output Current (Total)
20A(Max); 16A(UL de-rated)
Maximum Output Current (Total)
16A(Max)
Breakers
1 x 20A Non-Fuse Breaker
Breakers
1 x 20A Non-Fuse Breaker
Breakers
1 x 16A Non-Fuse Breaker
Metering
Bank level Current, Voltage, VA , PF and KWh Monitoring
Metering
Bank level Current, Voltage, VA , PF and KWh Monitoring
Metering
Bank level Current, Voltage, VA , PF and KWh Monitoring
Outlet Switching
None
Outlet Switching
None
Outlet Switching
None
Environment Sensor Ports
2
Environment Sensor Ports
2
Environment Sensor Ports
2
Metering Accuracy
Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Metering Accuracy
Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Metering Accuracy
Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%

Physical Properties

Dimensions (L x W x H)
43.24 x 22.04 x 4.40 cm (17.02 x 8.68 x 1.73 in.)
Dimensions (L x W x H)
43.24 x 22.04 x 4.40 cm (17.02 x 8.68 x 1.73 in.)
Dimensions (L x W x H)
43.24 x 22.04 x 4.40 cm (17.02 x 8.68 x 1.73 in.)
Weight
2.71 kg ( 5.97 lb )
Weight
2.71 kg ( 5.97 lb )
Weight
2.71 kg ( 5.97 lb )
Power Cord Length
3 m
Power Cord Length
3 m
Power Cord Length
3 m

Environmental

Temperature (Operating / Storage)
0 – 50°C / -20 – 60°C
Temperature (Operating / Storage)
0 – 50°C / -20 – 60°C
Temperature (Operating / Storage)
0 – 50°C / -20 – 60°C
Humidity (Operating & Storage)
0 – 80% RH, Non-Condensing
Humidity (Operating & Storage)
0 – 80% RH, Non-Condensing
Humidity (Operating & Storage)
0 – 80% RH, Non-Condensing

Compliance

EMC Verification
FCC, Others by Request
EMC Verification
FCC, Others by Request
EMC Verification
CE, Others by Request
Safety Verification
UL, Others by Request
Safety Verification
UL, Others by Request
Safety Verification
CE-LVD, Others by Request
Note
For some of rack mount products, please note that the standard physical dimensions of WxDxH are expressed using a LxWxH format.

Firmware

Similar products