Skip to content

Basic 1U PDU with surge protection

PE0110S

Basic 1U rack PDU with surge protection, distributing power to rack equipment; aluminum housing, available with IEC or NEMA outlets, rated up to 15 A input.

Features

  • Space saving -1U rack mount design
  • IEC or NEMA outlet models
  • Surge Protection
  • Aluminum material
  • Works with data centers, server rooms and telecom equipment

Electrical

Nominal Input Voltage
100-120 VAC
Nominal Input Voltage
100-240 VAC
Maximum Input Current
15A (Max) (UL de-rated 12A Max) (PSE 10A)
Maximum Input Current
10A (Max)
Input Frequency
50-60 Hz
Input Frequency
50-60 Hz
Input Connection
NEMA 5-15P
Input Connection
For G Plug:IEC-320 C14 For Z Plug:Chinese 10A
Input Power
1800VA(Max);1440VA(UL de-rated)
Input Power
2400VA(Max)
Outlet Type
(10) NEMA 5-15R
Outlet Type
(10) IEC-320 C13
Maximum Output Current (Outlet)
15A (Max) (UL de-rated 12A Max) (PSE 10A)
Maximum Output Current (Outlet)
10A (Max)
Maximum Output Current (Bank)
15A (Max) (UL de-rated 12A Max) (PSE 10A)
Maximum Output Current (Bank)
10A (Max)
Maximum Output Current (Total)
15A (Max) (UL de-rated 12A Max) (PSE 10A)
Maximum Output Current (Total)
10A (Max)
OPD(Overcurrent Protection Device)
YES
OPD(Overcurrent Protection Device)
YES

Physical Properties

Dimensions (L x W x H)
48.20 x 4.44 x 4.50 cm (18.98 x 1.75 x 1.77 in.)
Dimensions (L x W x H)
48.20 x 4.44 x 4.50 cm (18.98 x 1.75 x 1.77 in.)
Weight
0.66 kg ( 1.45 lb )
Weight
0.66 kg ( 1.45 lb )
Power Cord Length
10ft(14#)
Power Cord Length
10ft(3×1.5mm2)

Environmental

Temperature (Operating / Storage)
0 – 40℃ / -20 – 60℃ *When the environmental temperature comes close 40 degrees, it is recommended to lower the load to 60% to comply to the safety regulations.
Temperature (Operating / Storage)
0 – 40℃ / -20 – 60℃ *When the environmental temperature comes close 40 degrees, it is recommended to lower the load to 60% to comply to the safety regulations.
Elevation (Operating / Storage)
3000m
Elevation (Operating / Storage)
3000m

Compliance

EMC Verification
FCC Class A
EMC Verification
-
Safety Verification
UL
Safety Verification
LVD
Note
For some of rack mount products, please note that the standard physical dimensions of WxDxH are expressed using a LxWxH format.

Similar products